Buy Schneider/Telemecanique LRD22 online at Wesco.ie - Part of our large Schneider Electric Industrial range of products. In stock for express delivery
TESYS D THERMAL OVERLOAD 16-24A CL10A
Thermal overload relay, TeSys LRD, 16...24 A, class 10A
Thermal overload relay, TeSys LRD, 16...24 A, class 10A TeSys LRD thermal overload relay, 24A/690V, thermal setting range 16-24A, tripping class 10A, for protection of 3-phase motors 11kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustment dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing.
Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D25-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
Adjustable current range: | 16...24 A |
---|---|
Max. rated operation voltage Ue: | 690 V |
Mounting method: | Direct attachment |
Number of auxiliary contacts as change-over contact: | 0 |
Number of auxiliary contacts as normally closed contact: | 1 |
Number of auxiliary contacts as normally open contact: | 1 |
Release class: | CLASS 10 A |
Type of electrical connection of main circuit: | Screw connection |
Reset function automatic: | Yes |
Reset function input: | false |
Reset function push-button: | Yes |